Breaker duty setting parameters, Relay data setting parameters, Breaker duty setting parameters -15 – Basler Electric BE1-700 Modbus Protocol User Manual

Page 63: Relay data setting parameters -15

Advertising
background image

9376700991 Rev D

BE1-700 Modbus™ Protocol

3-15

41039-40

VT Connection

ASC(3)

Read and Write:

3W for 3W

4W for 4W

AB for AB

BC for BC

CA for CA

AN for AN

BN for BN

CN for CN

41043-44

VT Auxiliary Connection

ASC(3)

Read and Write:

AB for AB

BC for BC

CA for CA

AN for AN

BN for BN

CN for CN

GR for GR

Breaker Duty Setting Parameters

41092-93

Breaker Duty Exponent

FP

Read and Write:

1.000 to 3.000

41094-95

Maximum Breaker Duty

FP

Read and Write: 0 to 42,900,000 amps

41096

Programmable Breaker Alarm #1 Mode

INT

41099

Programmable Breaker Alarm #2 Mode

INT

41102

Programmable Breaker Alarm #3 Mode

INT

Read and Write:

0 for Disabled

1 for Percent duty

2 for Breaker operations

3 for Clearing time

41097-98

Programmable Breaker Alarm #1 Limit

FP

41100-01

Programmable Breaker Alarm #2 Limit

FP

41103-04

Programmable Breaker Alarm #3 Limit

FP

Read and Write:

If mode is 0: Reads 0, any value writes 0

If mode is 1: 0.00 to 100.00%

If mode is 2: 0 to 99,999

If mode is 3: 0, 20 to 1000 milliseconds

Relay Data Setting Parameters

41247

Volts / Hertz alarm settings

INT

Read and Write: 0 to 120 percent

41248-49

Volts/Hertz alarm time delay

LI

Read and Write: 50 to 600,000 milliseconds

41259-60

Phase Demand Alarm Level

FP

41261-62

Neutral Demand Alarm Level

FP

41263-64

Negative-Sequence Demand Alarm Level

FP

Read and Write: 0.00 to 16.00 amps