Breaker duty setting parameters, Relay data setting parameters, Breaker duty setting parameters -15 – Basler Electric BE1-700 Modbus Protocol User Manual
Page 63: Relay data setting parameters -15
9376700991 Rev D
BE1-700 Modbus™ Protocol
3-15
41039-40
VT Connection
ASC(3)
Read and Write:
3W for 3W
4W for 4W
AB for AB
BC for BC
CA for CA
AN for AN
BN for BN
CN for CN
41043-44
VT Auxiliary Connection
ASC(3)
Read and Write:
AB for AB
BC for BC
CA for CA
AN for AN
BN for BN
CN for CN
GR for GR
Breaker Duty Setting Parameters
41092-93
Breaker Duty Exponent
FP
Read and Write:
1.000 to 3.000
41094-95
Maximum Breaker Duty
FP
Read and Write: 0 to 42,900,000 amps
41096
Programmable Breaker Alarm #1 Mode
INT
41099
Programmable Breaker Alarm #2 Mode
INT
41102
Programmable Breaker Alarm #3 Mode
INT
Read and Write:
0 for Disabled
1 for Percent duty
2 for Breaker operations
3 for Clearing time
41097-98
Programmable Breaker Alarm #1 Limit
FP
41100-01
Programmable Breaker Alarm #2 Limit
FP
41103-04
Programmable Breaker Alarm #3 Limit
FP
Read and Write:
If mode is 0: Reads 0, any value writes 0
If mode is 1: 0.00 to 100.00%
If mode is 2: 0 to 99,999
If mode is 3: 0, 20 to 1000 milliseconds
Relay Data Setting Parameters
41247
Volts / Hertz alarm settings
INT
Read and Write: 0 to 120 percent
41248-49
Volts/Hertz alarm time delay
LI
Read and Write: 50 to 600,000 milliseconds
41259-60
Phase Demand Alarm Level
FP
41261-62
Neutral Demand Alarm Level
FP
41263-64
Negative-Sequence Demand Alarm Level
FP
Read and Write: 0.00 to 16.00 amps