41284

Output Hold Mask

BM(8)

Read and Write:

Bit 7 - Spare

Bit 6 - Spare

Bit 5 - Output 5 Status

Bit 4 - Output 4 Status

Bit 3 - Output 3 Status

Bit 2 - Output 2 Status

Bit 1 - Output 1 Status

Bit 0 - Output A Status

41285

Target Mask MSBs

BM(16)

Read and Write:

Bit 15 - 151C

Bit 14 - 151B

Bit 13 - 151A

Bit 12 - 51C

Bit 11 - 51B

Bit 10 - 51A

Bit 9 - 150TQ

Bit 8 - 50TQ

Bit 7 - 150TN

Bit 6 - 50TN

Bit 5 - 150TC

Bit 4 - 150TB

Bit 3 - 150TA

Bit 2 - 50TC

Bit 1 - 50TB

Bit 0 - 50TA

41286

Target Mask Second MSBs

BM(16)

Read and Write:

Bit 15 - BF

Bit 14 - 47

Bit 13 - Spare

Bit 12 - Spare

Bit 11 - Spare

Bit 10 - Spare

Bit 9 - Spare

Bit 8 - Spare

Bit 7 - 27X

Bit 6 - 127C

Bit 5 - 127B

Bit 4 - 127A

Bit 3 - 27C

Bit 2 - 27B

Bit 1 - 27A

Bit 0 - 24

41287

Target Mask Third MSBs

BM(16)

Read and Write:

Bit 15 - 581

Bit 14 - 481

Bit 13 -381

Bit 12 - 281

Bit 11 - 181

Bit 10 - 81

Bit 9 - Spare

Bit 8 - Spare

Bit 7 - Spare

Bit 6 - Spare