Fault template (flt), Report template (rpt), Metering parameters – Basler Electric BE1-700 Modbus Protocol User Manual

Page 45

Advertising
background image

Holding

Read/Write

Data

Register

Parameter

Supported

Format

Notes

9376700991 Rev D

BE1-700 Modbus™ Protocol

2-17

47475-76

Peak Demand Current Since Reset-Neutral

R W

FP

47477

Peak Demand Since Reset Timestamp-day

R –

INT

TS

47478-79

Peak Demand Since Reset Timestamp-ms

R –

LI

TS

47480-81

Peak Demand Current Since Reset-Neg-Seq

R W

FP

47482

Peak Demand Since Reset Timestamp-day

R –

INT

TS

47483-84

Peak Demand Since Reset Timestamp-ms

R –

LI

TS

47486

Reset Logic Alarm Information

R W

SI

47487

Reset Major Alarm Information

R W

SI

47488

Reset Minor Alarm Information

R W

SI

47489

Reset Relay Alarm Information

R W

SI

47491

Clear Fault Log

R W

SI

47492

Trigger Fault Record

R W

SI

47493

Clear Events Report

R W

SI

47512

Fault Indicator

R –

SI

47513

Fault Template Status

R –

SI

47514

Fault Date and Time - day

R –

INT

FLT, TS

Fault Template (FLT)

47515-16

Fault Date and Time - milliseconds

R –

LI

FLT, TS

47517

Fault Event Type

R –

BM(16)

FLT

47518

Fault Active Group

R –

SI

FLT

47519-24

Fault Targets

R –

BM(96)

FLT

47525

Fault Clearing Time Status

R –

SI

FLT

47526-27

Fault Clearing Time

R –

FP

FLT

47528

Fault Breaker Operate Time Status

R –

SI

FLT

47529-30

Fault Breaker Operate Time

R –

FP

FLT

47532-33

Fault Phase A Current Magnitude

R –

FP

FLT

47535-36

Fault Phase B Current Magnitude

R –

FP

FLT

47538-39

Fault Phase C Current Magnitude

R –

FP

FLT

47541-42

Fault Ground Current Magnitude

R –

FP

FLT

47546-47

Fault Phase A Voltage Magnitude

R –

FP

FLT

47548-49

Fault Phase B Voltage Magnitude

R –

FP

FLT

47550-51

Fault Phase C Voltage Magnitude

R –

FP

FLT

47552-53

Fault Vx Voltage Magnitude

R –

FP

FLT

47556-57

Fault Generator Frequency

R –

FP

FLT

47558-59

Fault Bus Frequency

R –

FP

FLT

47595-719

Report Text

R –

ASC(250)

RPT

Report Template (RPT)

49719

Part Number

R –

INT

Metering Parameters

49720-21

Generator Frequency

R –

FP

49722-23

Bus Frequency

R –

FP

49724-25

Slip Frequency

R –

FP

Advertising