Basler Electric BE1-700 Modbus Protocol User Manual

Page 50

Advertising
background image

3-2

BE1-700 Modbus™ Protocol

9376700991 Rev D

41809

Programmable 62 Timer Logic Mode

INT

41842

Programmable 162 Timer Logic Mode

INT

Read and Write:

0 for disabled

1 for Pickup / Dropout

2 for One-Shot Non-Retriggerable

3 for One-Shot Retriggerable

4 for Oscillator

5 for Integrating

6 for Edge Triggered Latch

41875

Programmable 27P Logic Mode

INT

41909

Programmable 127P Logic Mode

INT

41943

Programmable 59P Logic Mode

INT

41977

Programmable 159P Logic Mode

INT

Read and Write:

0 for disabled

1 for enabled - Undervoltage or overvoltage on one or more phases causes pickup

2 for enabled - Undervoltage or overvoltage on two or more phases causes pickup

3 for enabled - Undervoltage or overvoltage on all three phases causes pickup

41892

Programmable 27X Logic Mode

INT

41960

Programmable 59X Logic Mode

INT

41994

Programmable 159X Logic Mode

INT

Read and Write:

0 for disabled

1 for enabled - Fundamental Vx input

2 for enabled - 3Vo phase input

3 for enabled - 3

rd

harmonic, Vx input

43236

Programmable 81 Logic Mode

INT

43253

Programmable 181 Logic Mode

INT

43270

Programmable 281 Logic Mode

INT

43287

Programmable 381 Logic Mode

INT

43304

Programmable 481 Logic Mode

INT

43321

Programmable 581 Logic Mode

INT

Read and Write:

0 for disabled

1 for enabled

43338

Programmable 47 Logic Mode

INT

Read and Write:

0 for disabled

1 for enabled

43355

Programmable 24 Logic Mode

INT

Read and Write:

0 for disabled

1 for enabled

43372

Programmable 25 Logic Mode

INT

Read and Write:

0 for disabled

1 for enabled

42062

Programmable Settings Group Logic Mode

INT

Read and Write:

0 for all setting groups disabled except Group 0

1 for selecting setting group via pulsed input logic

2 for selecting setting group via sustained input logic