Logic term count, Session parameters, Template parameters – Basler Electric BE1-700 Modbus Protocol User Manual

Page 53: Logic term count -5, Session parameters -5, Template parameters -5

Advertising
background image

9376700991 Rev D

BE1-700 Modbus™ Protocol

3-5

Bit 1 - 159X tripped

Bit 0 - 59X tripped

Bit 0 - 159 phase tripped

Logic Term Count

Term Count Register

SI

0

means the logic equation is disabled (NONE)

-1

means the logic equation consists of a single term of OR-ed variables

1

means the logic equation consists of a single term of AND-ed variables

2

means the logic equation consists of the OR-ing of 2 terms of AND-ed variables

3

means the logic equation consists of the OR-ing of 3 terms of AND-ed variables

4

means the logic equation consists of the OR-ing of 4 terms of AND-ed variables

Session Parameters

40001

Exit

ASC(1)

Read: Always the ASCII character '0' (zero)

Write: ASCII characters 'Y' or 'N' ('Y' to save changes, 'N' to ignore changes)

Note 1: ERROR DETAIL block (49835-54) contains Exit status message following a write.

Note 2: Writing to this register is effective only when Password Security register 40989 is

enabled.

40002-5

Access Password

ASC(8)

Read: Always the ASCII string of '*' characters.

Write: Access password in ASCII string.

Note 1: If password written is less than 8 characters long, a binary zero value must be

included following the final password character.

Note 2: Writing to this register is effective only when Password Security register 40989 is

enabled.

40006

Access Request

BM(16)

Read: Returns the current write access available to the Modbus user

Bit 3 is set for Global Access

Bit 2 is set for Setting Access

Bit 1 is set for Control Access

Bit 0 is set for Report Access

Zero value for Read Only Access

Write: To request write privileges using the password written into Access Password registers.

Value written into Access Request register is arbitrary (any value will initiate the request).

Note 1: If write access is denied, the response message will be an error response

message with Illegal Function exception code.

Step1. Write the desired password to PASSWORD registers 40002 to 40005

Step2. Write any value to ACCESS REQUEST register 40006

Step3. Read Access Level from ACCESS REQUEST register 40006

Note 2: Writing to this register is effective only when Password Security register 40989 is

enabled.

Template Parameters

40036

Settings Group Selection

SI

Read: Returns the current value of Settings Group Selection.

Write: The desired value to assign a Settings Group to the Group (GRP) Template.

O for Settings Group 0

1 for Settings Group 1

40038

Fault Selection

SI

Read: Returns the current value of Fault Selection.

Write: The desired value to assign a Fault Record to the Fault (FLT) Template. Allowed values

are 1 - 255.

Note: Refer to Fault Indicator (47512) and Fault Template Status (47513) Registers.