9376700991 Rev D

BE1-700 Modbus™ Protocol

1-13

Preset Single Register (Write Single Holding Register)

A Preset Single Register query message requests a single register to be written. The BE1-700 will

perform the write when the device address is the same as the BE1-700's remote address.

Data will cease to be written if any of the following exceptions occur:

Query

Queries to write to Read Only registers result in an error response with Exception Code of Illegal

Data Address.

A query to write an unallowed value (out of range) to a register results in an error response with

Exception Code of "Illegal Data Value.”

Device Address

Function Code =

06 (hex)

Address Hi

Address Lo

Data Hi

Data Lo

CRC Hi error check

CRC Lo error check

The response message echoes the Query message after the register has been altered.

Response

Data Formats

BE1-700 data varies from one to four bytes in length. Single byte data resides in the holding register

least-significant byte with the most-significant byte set to zero. Floating point data and long integer data

(each 32-bits in length) place the two most-significant bytes in the higher holding register address of the

associated register pair.

Floating Point Data Format (FP)

The Modbus floating point data format uses two consecutive holding registers to represent a data value.

The first register contains the low-order 16 bits of the following 32 bit format:

MSB is the sign bit for the floating point value (0 = positive).

The next 8 bits are the exponent biased by 127 decimal.

The 23 LSBs comprise the normalized mantissa. The most-significant bit of the mantissa is

always assumed to be 1 and is not explicitly stored, yielding an effective precision of 24 bits.


The value of the floating point number is obtained by multiplying the binary mantissa times two raised to

the power of the unbiased exponent. The assumed bit of the binary mantissa has the value of 1.0, with

the remaining 23 bits providing a fractional value. Table 1-3 shows the floating point format.

Table 1-3. Floating Point Format

Sign

Exponent +127

Mantissa

1 bit

8 bits

23 bits


The floating point format allows for values ranging from approximately 8.43X10-37 to 3.38X1038. A

floating point value of all zeroes is the value zero. A floating point value of all ones (not a number)

signifies a value currently not applicable or disabled.
Example: The value 95,800 represented in floating point format is hexadecimal 47BB1C00. This number

will read from two consecutive holding registers as follows:
Holding Register

K (Hi Byte)

hex 1C

Value

K (Lo Byte)

hex 00

K+1 (Hi Byte)

hex 47

K+1 (Lo Byte)

hex BB