Introduction, Procedure, Appendix a – Basler Electric BE1-700 Modbus Protocol User Manual

Page 87

Advertising
background image

9376700991 Rev D

BE1-700 Modbus™ Protocol

A-1

APPENDIX A • SETTING UP A DHCP SERVER

BETWEEN BE1-700 AND PC

Introduction

This appendix explains how to set up a DHCP server using a BE1-700 with Modbus/TCP and a crossover

Ethernet cable. A downloadable freeware program, Tftpd32, is required.

Procedure

1. Direct your browser to

http://tftpd32.jounin.net

and download the Tftpd32 v4.00 software installation

file. After download completes, install the software.

2. Connect the Ethernet port of your PC directly to the Ethernet port of the BE1-700 using an Ethernet

crossover cable (must NOT be a standard Ethernet cable).

3. Verify that your PC’s network adapter is set to a static IP address such as 10.0.1.55 (10.0.1.x). Open

the Control Panel  Network Connections on your computer. Right click on the network adapter

being used and select Properties. In the center of the Local Area Connection Properties dialog box,

scroll down and double-click on Internet Protocol (TCP/IP). Record your existing settings and then set

the following parameters shown in Figure A-1.

Figure A-1. Internet Protocol (TCP/IP) Properties Screen


4. Start Tftpd32 and click the Settings button. On the Global tab, enable only the

DHCP Server. See

Figure A-2.

Advertising