Serial port setting parameters, System data setting parameters, Breaker duty setting parameters – Basler Electric BE1-700 Modbus Protocol User Manual

Page 34

Advertising
background image

Holding

Read/Write

Data

Register

Parameter

Supported

Format

Notes

2-6

BE1-700 Modbus™ Protocol

9376700991 Rev D

40872

Setting Group 1 Automatic Control Switch Time R W

SI

40873

Setting Group 1 Automatic Control Switch Level R W

SI

40874

Setting Group 1 Automatic Control Time

R W

SI

40875

Setting Group 1 Automatic Control Return Level R W

SI

40876

Setting Group 1 Tracking Element

R W

INT

40887-92

79 Zone-Sequence Logic Mask

R W

BM(96)

40895-900

79 Zone-Sequence Logic Term

R W

BM(96)

40903-04

60FL Loss of Pot. Current Auto Block Setting

R W

ASC(3)

40905-06

60FL Loss of Potential Volt. Auto Block Setting R W

ASC(3)

40962

Serial Port 0 Baud Rate

R W

INT

Serial Port Setting Parameters

40964

Serial Port 0 Software Flow Control

R W

SI

40965

Serial Port 0 Page Length

R W

SI

40966

Serial Port 0 Acknowledgement Format

R W

SI

40980

Serial Port 2 Baud Rate

R W

INT

40981

Serial Port 2 Relay Address

R W

INT

40986

Serial Port 2 Modbus Parity

R W

SI

40987

Serial Port 2 Modbus Remote Delay

R W

SI

40988

Serial Port 2 Modbus Stop Bits

R W

SI

40989

Password Security

R W

SI

41018

System Frequency

R W

SI

System Data Setting Parameters

41019-20

Phase Rotation

R W

ASC(3)

41021

Phase Ratio

R W

INT

41022

Ground CT Ratio

R W

INT

41033-34

Phase VT Ratio

R W

FP

41035-36

27/59 Voltage Sensing Mode

R W

ASC(3)

41037-38

51/27R Voltage Sensing Mode

R W

ASC(3)

41039-40

VT Connection

RW

ASC(3)

41041-42

Auxiliary VT Ratio

R W

FP

41043-44

VT Auxiliary Connection

RW

ASC(3)

41046-47

Power Line - Z1 Impedance

R W

FP

41048-49

Power Line - Z1 Angle

R W

FP

410450-51

Power Line - Z0 Impedance

R W

FP

41052-53

Power Line - Z0 Angle

R W

FP

41054-55

Power Line - Line Length

R W

FP

41092-93

Breaker Duty Exponent

R W

FP

Breaker Duty Setting Parameters

41094-95

Maximum Breaker Duty

R W

FP

41096

Programmable Breaker Alarm #1 Mode

R W

INT

41097-98

Programmable Breaker Alarm #1 Limit

R W

FP

41099

Programmable Breaker Alarm #2 Mode

R W

INT

41100-01

Programmable Breaker Alarm #2 Limit

R W

FP