Basler Electric BE1-700 Modbus Protocol User Manual

Page 60

Advertising
background image

3-12

BE1-700 Modbus™ Protocol

9376700991 Rev D

40498-99

27P Pickup

FP

40510-11

127P Pickup

FP

Read and Write: 10.0 to 300

40504-05

27X Pickup

FP

Read and Write: 1.00 to 150

40500-01

27P Time Delay

LI

40506-07

27X Time Delay

LI

40512-13

127P Time Delay

LI

Read and Write: 50 to 600,000 milliseconds

40502-03

27P Inhibit Voltage

FP

40514-15

127P Inhibit Voltage

FP

Read and Write: 10.0 to 300

40508-09

27X Inhibit Voltage

FP

Read and Write: 1.00 to 150

40516-17

24 Pickup

FP

Read and Write: 0.50 to 6.00

40518-19

24 Time Delay

FP

40520-21

24 Reset Delay

FP

Read and Write: 0 to 9.9

40522-23

24 Definite Timer 1 Pickup

FP

40526-27

24 Definite Timer 2 Pickup

FP

Read and Write: 0.50 to 6.00

40524-25

24 Definite Timer 1 Time Delay

FP

40528-29

24 Definite Timer 2 Time Delay

FP

Read and Write: 50 to 600000

40530-31

24 Curve Type

ASC(3)

Read and Write: 0.5, 1 or 2

40532-33

25 Delta Volts

FP

Read and Write: 1.0 to 20.0

40534-35

25 Phase Angle

FP

Read and Write: 1 to 45

40536-37

25 Slip Frequency

FP

Read and Write: 0 to 0.5 Hz

40538

25 Mode

LI

Read and Write: 1 = GF>BF, 0 = GF<>BF

40539-40

25 VM Live Volts

FP

40541-42

25 VM Dead Volts

FP

Read and Write: 10.0 to 150

40543-44

25 VM Time Delay

LI

Read and Write: 50 to 60,000 milliseconds

40545-46

25 VM Mode 1

ASC(3)

Read and Write: 1,2, and/or 3, DIS