3-4

BE1-700 Modbus™ Protocol

9376700991 Rev D

Bit 9 - Virtual Output 9 status

Bit 8 - Virtual Output 8 status

Bit 7 - Virtual Output 7 status

Bit 6 - Virtual Output 6 status

Bit 5 - Virtual Output 5 status

Bit 4 - Virtual Output 4 status

Bit 3 - Virtual Output 3 status

Bit 2 - Virtual Output 2 status

Bit 1 - Virtual Output 1 status

Bit 0 - Virtual Output A status

Mask and Term - Fourth Register (Logic Var 48 to 63)

BM(16)

Bit 15 - Target Reset key

Bit 14 - Output circuit monitor

Bit 13 - Alarm minor

Bit 12 - Alarm major

Bit 11 - Alarm logic

Bit 10 - 101 SC

Bit 9 - 101C

Bit 8 - 101T

Bit 7 - 27 neutral picked-up

Bit 6 - 27 neutral tripped

Bit 5 - 162

Bit 4 - 62

Bit 3 - Input 4 status

Bit 2 - Input 3 status

Bit 1 - Input 2 status

Bit 0 - Input 1 status

Mask and Term - Fifth Register (Logic Var 64 to 79)

BM(16)

Bit 15 – 59 phase tripped

Bit 14 - BF tripped

Bit 13 – BF picked-up

Bit 12 - 24 volts per hertz picked-up

Bit 11 – 24 volts per hertz tripped

Bit 10 - 47 picked-up

Bit 9 - 47 tripped

Bit 8 - 127 phase picked up

Bit 7 - 27 phase picked up

Bit 6 - 127 phase tripped

Bit 5 - 27 phase tripped

Bit 4 - 159 phase picked-up

Bit 3 - 59 phase picked-up

Bit 2 - Settings Group 1

Bit 1 - Settings Group 0

Bit 0 - Alarm Reset key

Mask and Term - Sixth Register (Logic Var 80 to 95)

BM(16)

Bit 15 - Spare

Bit 14 - Spare

Bit 13 - 25 tripped

Bit 12 - 25 voltage monitor 1 pickup

Bit 11 - 60FL

Bit 10 - 581 tripped

Bit 9 - 481 tripped

Bit 8 - 381 tripped

Bit 7 - 281 tripped

Bit 2 - 181 tripped

Bit 1 - 81 tripped

Bit 0 - 159X picked-up

Bit 0 - 59X picked-up