BE1-700 Modbus™ Protocol

9376700991 Rev D

40135

Select 101 Virtual Breaker Control Switch

ASC(1)

Read: To read a value other than ASCII character 'X,' the Select 101 Virtual Breaker Control

Switch register must be the most recent control register written AND must have been

written within the previous 30 seconds.

C if Close selection has been made.

T if Trip selection has been made.

X if 101 Virtual Breaker Control Switch control not selected or control timer has expired.

Write: The desired ASCII character.

C to select Closing the Switch.

T to select Tripping the Switch.

40136

Operate 101 Virtual Breaker Control Switch

ASC(1)

Read: Current control.

C if Close Switch.

T if Trip Switch.

Write: The desired ASCII character to alter control (corresponding Select register must contain

same value, written within previous 30 seconds).

C to Close Switch.

T to Trip Switch.

40137

Select All Outputs

ASC(1)

Read: To read a value other than ASCII character 'X,' the Select All Output register must be the

most recent control register written AND must have been written within the previous 30

seconds.

P if Pulse All Outputs selection has been made.

0 if Latch All Outputs at 0 selection has been made.

1 if Latch All Outputs at 1 selection has been made.

L if programmable Logic selection has been made.

E if Enable All Outputs override control has been set.

D if Disable All Outputs override control has been set.

X if All Outputs control not selected or control timer has expired.

Write: The desired ASCII character.

P to select Pulsing All Outputs.

0 to select Latching All Outputs at 0.

1 to select Latching All Outputs at 1.

L to select programmable Logic.

E to select Enabling All Outputs override control.

D to select Disabling All Outputs override control.

40138

Operate All Outputs

ASC(1)

Read: Current control.

E if All Outputs override control Enabled.

D if All Outputs override control Disabled.

Write: The desired ASCII character to alter control (corresponding Select register must contain

same value, written within previous 30 seconds).

P to Pulse All Outputs.

0 to Latch All Outputs at 0.

1 to Latch All Outputs at 1.

L to select programmable Logic.

E to Enable All Outputs override control. ∗

D to Disable All Outputs override control. ∗

40139

Select Output A

ASC(1)

40141

Select Output 1

ASC(1)

40143

Select Output 2

ASC(1)

40145

Select Output 3

ASC(1)

40147

Select Output 4

ASC(1)

40149

Select Output 5

ASC(1)