Control parameters, Control parameters -7 – Basler Electric BE1-700 Modbus Protocol User Manual

Page 55

Advertising
background image

9376700991 Rev D

BE1-700 Modbus™ Protocol

3-7

Control Parameters

All values read from and written to Select and Operate registers are ASCII characters. Select registers

must be written first, followed by a write to the Operate register. A 30 second window starts after the first

write to the Select register. If the second write to the Operate register is not received within the 30 second

window, an error response will be returned.
Writes to Operate registers 40138, 40140 - 40150 with ASCII data 'E ' (Enable Output override control) or

'D' (Disable Output override control) requires an additional write of 'Y' to Exit register 40001 to allow these

control settings to be saved to the relay internal EEPROM.
NOTE: All values read from and written to Select and Operate registers are ASCII characters.

40117

Select Group

ASC(1)

Read: To read a value other than ASCII character 'X', the Select Group register must be the most

recent control register written AND must have been written within the previous 30

seconds.

0 if Group 0 selection has been made.

1 if Group 1 selection has been made.

L if Logic selection has been made.

X if Group control not selected or control timer has expired.

Write: The desired ASCII character.

0 to select Group 0.

1 to select Group 1.

L to select Logic.

40118

Operate Group

ASC(1)

Read: Current control.

0 if Group 0.

1 if Group 1.

L if Logic.

Write: The desired ASCII character to alter control (corresponding Select register must contain

same value, written within previous 30 seconds).

0 to select Group 0.

1 to select Group 1.

L to select Logic.

40119

Select Virtual Selector Switch 43

ASC(1)

40121

Select Virtual Selector Switch 143

ASC(1)

Read: To read a value other than ASCII character 'X,' the Select Virtual Selector Switch register

must be the most recent control register written AND must have been written within the

previous 30 seconds.

P if Pulse Switch selection has been made.

0 if Latch Switch at 0 selection has been made.

1 if Latch Switch at 1 selection has been made.

X if Virtual Selector Switch control not selected or control timer has expired.

Write: The desired ASCII character.

P to select Pulsing the Switch.

0 to select Latching the Switch at 0.

1 to select Latching the Switch at 1.

40120

Operate Virtual Selector Switch 43

ASC(1)

40122

Operate Virtual Selector Switch 143

ASC(1)

Read: Current control.

P if Pulse Switch.

0 if Latch Switch at 0.

1 if Latch Switch at 1.

Write: The desired ASCII character to alter control (corresponding Select register must contain

same value, written within previous 30 seconds).

P to Pulse Switch.

0 to Latch Switch at 0, 1 to Latch Switch at 1.