Basler Electric BE1-700 Modbus Protocol User Manual

Page 69

Advertising
background image

9376700991 Rev D

BE1-700 Modbus™ Protocol

3-21

47370

System Status (Logic Var 48 to 63)

BM(16)

Read only:

Bit 15 - Target Reset key

Bit 14 - Output circuit monitor

Bit 13 - Alarm minor

Bit 12 - Alarm major

Bit 11 - Alarm logic

Bit 10 - 101 SC

Bit 9 - 101C

Bit 8 - 101T

Bit 7 - 27X picked-up

Bit 6 - 27X tripped

Bit 5 - 162

Bit 4 - 62

Bit 3 - Input 4 status

Bit 2 - Input 3 status

Bit 1 - Input 2 status

Bit 0 - Input 1 status

47371

System Status (Logic Var 64 to 79)

BM(16)

Read only:

Bit 15 - 59 phase tripped

Bit 14 - BF tripped

Bit 13 - BF picked up

Bit 12 - 24 picked up

Bit 11 - 24 tripped

Bit 10 - 47 picked-up

Bit 9 - 47 tripped

Bit 8 - 127 phase picked-up

Bit 7 - 27 phase picked-up

Bit 6 - 127 phase tripped

Bit 5 - 27 phase tripped

Bit 4 - 159 phase picked-up

Bit 3 - 59 phase picked-up

Bit 2 - Settings Group 1

Bit 1 - Settings Group 0

Bit 0 - Alarm Reset key

47372

System Status (Logic Var 80 to 95)

BM(16)

Read only:

Bit 15 - Spare

Bit 14 - Spare

Bit 13 - 25 tripped

Bit 12 - 25 Voltage Monitor 1

Bit 11 - 60FL

Bit 10 - 581 tripped

Bit 9 - 481 tripped

Bit 8 - 381 tripped

Bit 7 - 281 tripped

Bit 6 - 181 tripped

Bit 5 - 81 tripped

Bit 4 - 159X picked-up

Bit 3 - 59X picked-up

Bit 2 - 159X tripped

Bit 1 - 59X tripped

Bit 0 - 159 phase tripped

47373

Current Active Group Setting

SI

Read only: 0 or 1