BE1-700 Modbus™ Protocol

3-11

40429-30

27R Pickup

FP

Read and Write: 30.0 to 250

40431

27R Control Mode

ASC(1)

Read and Write: R or C

40432-33

47 Pickup

FP

Read and Write: 1 to 300

40434-35

47 Time Delay

LI

Read and Write 50 to 600,000 milliseconds

40436-37

59P Pickup

FP

40440-41

59X Pickup

FP

40444-45

159P Pickup

FP

40448-49

159X Pickup

FP

Read and Write: 10.0 to 300

40438-39

59P Time Delay

LI

40442-43

59X Time Delay

LI

40446-47

159P Time Delay

LI

40450-51

159X Time Delay

LI

Read and Write 50 to 600,000 milliseconds

40460-61

81 Pickup

FP

40465-66

181 Pickup

FP

40470-71

281 Pickup

FP

40475-76

381 Pickup

FP

40480-81

481 Pickup

FP

40485-86

581 Pickup

FP

Read and Write: 40.00 to 70.00 Hz

40462-63

81 Time Delay

LI

40467-68

181 Time Delay

LI

40472-73

281 Time Delay

LI

40477-78

381 Time Delay

LI

40482-83

481 Time Delay

LI

40487-88

581 Time Delay

LI

Read and Write: 0 to 600,000 milliseconds

40464

81 Mode

ASC(1)

40469

181 Mode

ASC(1)

40474

281 Mode

ASC(1)

40479

381 Mode

ASC(1)

40484

481 Mode

ASC(1)

40489

581 Mode

ASC(1)

Read and Write: O = overfrequency, U = underfrequency

R = Rate of Change

40490-91

81 Phase A Voltage Inhibit Setting

FP

Read and Write: 15.0 to 150 volts

40492-93

81 Neg-Seq. Voltage Inhibit Setting

FP

Read and Write: 0 to 99% of Phase A Inhibit Setting

40494-95

81 Overfrequency Inhibit Setting

FP

40496-97

81 Underfrequency Inhibit Setting

FP

Read and Write: 46.0 to 64.0 Hz