Session parameters, Template parameters, Global parameters – Basler Electric BE1-700 Modbus Protocol User Manual

Page 30: Control parameters

Advertising
background image

Holding

Read/Write

Data

Register

Parameter

Supported

Format

Notes

2-2

BE1-700 Modbus™ Protocol

9376700991 Rev D

40001

Exit

R W

ASC(1)

PS

Session Parameters

40002-05

Access Password

R W

ASC(8)

PS

40006

Access Request

R W

BM(16)

PS

40036

Settings Group Selection

R W

SI

Template Parameters

40038

Fault Selection

R W

SI

40039

Report Selection

R W

SI

40040

Report Focus

R W

INT

40080-83

Global Password

R W

ASC(8)

PW

Global Parameters

40084

Global Path

R W

BM(8)

PW

40085-88

Setting Password

R W

ASC(8)

PW

40089

Setting Path

R W

BM(8)

PW

40090-93

Control Password

R W

ASC(8)

PW

40094

Control Path

R W

BM(8)

PW

40095-98

Report Password

R W

ASC(8)

PW

40099

Report Path

R W

BM(8)

PW

40117

Select Group

R W

ASC(1)

Control Parameters

40118

Operate Group

R W

ASC(1)

40119

Select Virtual Selector Switch 43

R W

ASC(1)

40120

Operate Virtual Selector Switch 43

R W

ASC(1)

40121

Select Virtual Selector Switch 143

R W

ASC(1)

40122

Operate Virtual Selector Switch 143

R W

ASC(1)

40135

Select 101 Virtual Breaker Control Switch

R W

ASC(1)

40136

Operate 101 Virtual Breaker Control Switch

R W

ASC(1)

40137

Select All Outputs

R W

ASC(1)

40138

Operate All Outputs

R W

ASC(1)

40139

Select Output A

R W

ASC(1)

40140

Operate Output A

R W

ASC(1)

40141

Select Output 1

R W

ASC(1)

40142

Operate Output 1

R W

ASC(1)

40143

Select Output 2

R W

ASC(1)

40144

Operate Output 2

R W

ASC(1)

40145

Select Output 3

R W

ASC(1)

40146

Operate Output 3

R W

ASC(1)

40147

Select Output 4

R W

ASC(1)

40148

Operate Output 4

R W

ASC(1)

40149

Select Output 5

R W

ASC(1)

40150

Operate Output 5

R W

ASC(1)

Advertising