Group setting parameters, Group setting parameters -9 – Basler Electric BE1-700 Modbus Protocol User Manual

Page 57

Advertising
background image

9376700991 Rev D

BE1-700 Modbus™ Protocol

3-9

Read: To read a value other than ASCII character 'X', the Select Output register must be the most

recent control register written AND must have been written within the previous 30

seconds.

P if Pulse Output selection has been made.

0 if Latch Output at 0 selection has been made.

1 if Latch Output at 1 selection has been made.

L if programmable Logic selection has been made.

E if Enable All Outputs serial control has been made.

D if Disable All Outputs serial control has been made.

X if Output control not selected or control timer has expired.

Write: The desired ASCII character.

P to select Pulsing Output.

0 to select Latching Output at 0.

1 to select Latching Output at 1.

L to select programmable Logic.

E to select Enabling All Outputs override control.

D to select Disabling All Outputs override control.

40140

Operate Output A

ASC(1)

40142

Operate Output 1

ASC(1)

40144

Operate Output 2

ASC(1)

40146

Operate Output 3

ASC(1)

40148

Operate Output 4

ASC(1)

40150

Operate Output 5

ASC(1)

Read: Current control.

P to Pulse Output.

0 to Latch Output at 0.

1 to Latch Output at 1.

L to select programmable Logic.

D if All Outputs override control Disabled

Write: The desired ASCII character to alter control (corresponding Select register must contain

same value, written within previous 30 seconds).

P to Pulse Output.

0 to Latch Output at 0.

1 to Latch Output at 1.

L to select programmable Logic.

E to Enable All Outputs override control. ∗

D to Disable All Outputs override control. ∗

Requires an additional write of 'Y' to Exit register 40001 to allow these control settings to be saved to

the relay internal EEPROM.

Group Setting Parameters

40259-60

50TP Pickup

FP

40264-65

50TN Pickup

FP

40269-70

50TQ Pickup

FP

40274-75

150TP Pickup

FP

40279-80

150TN Pickup

FP

40284-85

150TQ Pickup

FP

Read and Write: 0.50 to 150.00 amps

40261-62

50TP Time Delay

LI

40266-67

50TN Time Delay

LI

40271-72

50TQ Time Delay

LI

40276-77

150TP Time Delay

LI

40281-82

150TN Time Delay

LI

40286-87

150TQ Time Delay

LI

Read and Write: 0 to 60,000 milliseconds

40263

50TP Directional Mode

ASC(1)

40268

50TN Directional Mode

ASC(1)