Basler Electric BE1-700 Modbus Protocol User Manual

Page 58

Advertising
background image

3-10

BE1-700 Modbus™ Protocol

9376700991 Rev D

40273

50TQ Directional Mode

ASC(1)

40278

150TP Directional Mode

ASC(1)

40283

150TN Directional Mode

ASC(1)

40288

150TQ Directional Mode

ASC(1)

Read and Write:

R = Reverse

N = Neutral

F = Forward

40301-02

51P Pickup

FP

40308-09

51N Pickup

FP

40315-16

51Q Pickup

FP

40329-30

151N Pickup

FP

Read and Write: 0.50 to 16.00 amps

40303-04

51P Time Dial

FP

40310-11

51N Time Dial

FP

40317-18

51Q Time Dial

FP

40331-32

151N Time Dial

FP

Read and Write: 0.0 to 9.9

40305-06

51P Curve Type

ASC(3)

40312-13

51N Curve Type

ASC(3)

40319-20

51Q Curve Type

ASC(3)

40333-34

151N Curve Type

ASC(3)

Read and Write: one of the following ASCII strings

S1, S2, L1, L2, D, M, I1, I2, V1, V2, E1, E2, S1R, S2R, L1R, L2R, DR, MR, I1R, I2R,

V1R, V2R, E1R, E2R, A, B, C, G, F, P, AR, BR, CR, GR, FR, PR, 46, 46R

40307

51P Directional Mode

ASC(1)

40314

51N Directional Mode

ASC(1)

40321

51Q Directional Mode

ASC(1)

40335

151N Directional Mode

ASC(1)

Read and Write:

R = reverse

N = neutral

F = forward

40359-60

62 Time Delay 1

LI

40361-62

62 Time Delay 2

LI

40363-64

162 Time Delay 1

LI

40365-66

162 Time Delay 2

LI

Read and Write: 0 to 9,999,000 milliseconds

40406-07

79 First Automatic Reclose Delay

LI

40408-09

79 Second Automatic Reclose Delay

LI

40410-11

79 Third Automatic Reclose Delay

LI

40412-13

79 Fourth Automatic Reclose Delay

LI

40414-15

79 Reset Time Delay

LI

40416-17

79 Reclose Fail Time Delay

LI

40418-19

79 Maximum Reclose Time

LI

40420-21

79 Pilot Time Delay

LI

Read and Write: 100 to 600,000 milliseconds, 0 to disable

40422

79 Sequence Control

BM(16)

Read and Write:

Bit 0 to Block Shot #1

Bit 1 to Block Shot #2

Bit 2 to Block Shot #3

Bit 3 to Block Shot #4

Bit 4 to Block Shot #5