background image

5

4. HITACHI PLC

5-37

Co
nne

c

tio

n

to P

L

Cs

HIDIC-H: Switch Setting

Baud rate:

19200 bps

MODE switch:

To connect to both RS-232C and RS-422, set MODE switch to 9.
RS-232C (protocol 2 without port) RS-422 (protocol 2 with port)

ST No switch:

“0” for both

Ч10, Ч1

DIP switch

Available Memory

The available memory setting range varies depending on the PLC model. Be sure to set within the
range available with the PLC to be used. Use [TYPE] when assigning the indirect memory for macro
programs.

HIDIC-H

Switch

Setting

Contents

1

OFF

Bit length

2

OFF

Same as that set on V7 (normally 19200 bps)

3

ON

4

ON

5

ON

With parity

6

ON

Even

7

OFF

Stop bit 1

8

ON

With sumcheck

Memory

TYPE

Remarks

WR

(internal word output)

0

X

(external bit input)

1

WX as word device

Y

(external bit output)

2

WY as word device

L

(bit CPU link area)

3

WL as word device

M

(bit data area)

4

WM as word device

TC

(timer counter/elapsed time)

5

R

(relay)

6

TD

(timer counter/contact)

7

WN

(network input/output)

8