Transferring screen data, Barcode reader connection, Transferring screen data -32 – Hakko MONITOUCH V7 series User Manual

Page 49: Barcode reader connection -32

Advertising
background image

1-32

12. Modular Jack (MJ1/MJ2)

Transferring Screen Data

• Use modular jack 1 (MJ1) when transferring screen data.

• When [Editor Port] is selected for [Modular Jack 1] on the V-SFT editor, it is possible to

transfer data in the RUN mode because the RUN/STOP mode (on the Main Menu
screen) can be automatically selected. Also RUN/STOP mode is automatically
selected for on-line editing and simulation.

• When an option other than [Editor Port] is selected for [Modular Jack 1], select the

STOP mode (on the Main Menu screen) and transfer screen data. Simulation or on-line
editing is not available.

• When transferring screen data, use Hakko Electronics’ data transfer cable (V6-CP) 3 m

to connect the V7 series to a personal computer.

Barcode Reader Connection

• It is possible to receive the signal from a barcode reader by connecting the barcode

reader at the modular jack (MJ1/2) of the V7 series.

• To connect a barcode reader to the modular

jack (MJ1/2), use Hakko Electronics’ optional
cable (V6-BCD).

Length: 3 m
with modular plug

• Notes on Connection

- In the case of barcode readers with CTS and RTS control, it may be necessary to

install a jumper to RTS and CTS. Otherwise the barcode reader may not work
correctly.

- The external power supply (+5 V) is max. 150 mA. (Refer to page 1-29.)

• When using the barcode reader that was connected to V4 (MONITOUCH’s old version),

connect it to the D-sub 9-pin female connector using the V6-BCD cable as shown
below.

12345678

Brown: +5V
Red: 0V
Orange: RXD
Yellow: TXD

Pin No

1

2

3

4

5

6

7

8

9

CTS

RXD

TXD

RTS

SG

+5V

12345678

RTS

TXD

RXD

CTS

SG

+5V

Signal

Name

Orange: RXD

Signal

Name

* Install a jumper between

CTS and RTS.

Yellow: TXD

Red: 0

V

Brown: +5 V

D-sub 9-pin (female)

Barcode reader

Advertising