Send f0 c: f1 to: f2 – Hakko MONITOUCH V7 series User Manual

Page 172

Advertising
background image

4

1. Ethernet

4-21

Netw

or

k C

o

mm

uni
ca
tio
n

s

[SEND]

Words from the F0 memory are transferred to the server of the network table number
specified for F2. F1 designates the number of words to be transferred.

Usable Devices

SEND:

Send to server

SEND F0 C: F1 TO: F2

Example: Macro command at the V7 (B)

The macro command for V7 (B) to transfer data to server (A) is shown below.

[Contents]

Two words starting from $u100 in V7 (B) are transferred to server
(A).

Internal

Memory

PLC

Memory

Constant

Memory

Card

Indirect

Designation

Double-

word

IP Address

F0

F1

F2

[Description] SEND $u100

C: 2

TO: A

Top memory address
of the source

The number of words to
be transferred

Address of the target (Network table number)

<PLC:B>

Ethernet

<V7:B>

F1

F2

F3

F4

F5

F6

F7

SYSTEM

POWER

SEND

Server (A)

Application

<V7 (B)>

<PLC (B)>

Advertising