Self-loop Test

This is a signal test for communications through the CN1, MJ1 or MJ2 connector. Perform
this test if the communication is not successful when transferring screen data through MJ1,
connecting the PLC using CN1, or selecting multi-link 2, temperature controller/PLC2Way
or PLC for MJ1/2, or connecting the card recorder or serial extension I/O.

CN1: RS-232C Signal Test

Turn the [CN1] and [RS232C] switches on.

• SD/RD Test

Check the signals [SD] and [RD].
1. Install a jumper between pins 2 and 3 of CN1 on the backside of the V7 unit.
2. Press the [Self-Loop Test] switch. When the [OK] lamp lights up, the test is

successfully completed.

* If the [NG] lamp lights up, consult your local distributor.

• CTS/RTS Test

Check the signals [CTS] and [RTS].
1. Install a jumper between pins 4 (RTS) and 5 (CTS) of CN1 on the backside of the V7

unit.

2. Press the [RTS] switch and check that both [RTS] and [CTS] lamps light up at the

same time. Press the [RTS] switch again and check that both [RTS] and [CTS]
lamps go off at the same time.

CN1

RS232C

MJ1

RS485

MJ2

Communication Port

Self-Loop Test

CTS

RTS

NG

OK

Self-Loop Test

CTS

RTS

NG

OK

Self-Loop Test

CTS

RTS

NG

OK

Self-Loop Test

CTS

RTS

NG

OK

Self-Loop Test

CTS

RTS

NG

OK

Self-Loop Test

CTS

RTS

NG

OK

Advertising