The recommended communication parameter settings of the PLC and the V7 series is as follows:

KZ Series Link

Set the port with the port setting switch, the terminating resistance with terminator, and the
baud rate/data bit/parity/stop bit with SET B DIP switches.

KZ-A500 CPU (CPU Modular Port)

*1 For signal level RS-422, baud rate is fixed to 9600 bps.

Mistubishi A Series Link (Link Unit KZ-L10)

Set the port with the port setting switch, the terminating resistance with terminator, and the
baud rate/data bit/parity/stop bit with SET B DIP switches. For more information, refer to
the instruction manual for KZ-L10.

Item

Setting on PLC

V7 Comm. Parameter Setting

Port

0

0

Baud rate

19200 bps

19200 bps

Parity

Even

Even

Transmission code

Data length

7 (ASCII)

7

Stop bit

2

2

Terminating resistance

ON for RS-422

Item

Setting on PLC

V7 Comm. Parameter Setting

Port

0

0

Baud rate

9600 bps

9600 bps

*1

Parity

Odd

Odd

Transmission code

Data length

8

8

Stop bit

1

1

Terminating resistance

ON for RS-422

Item

Setting on PLC

V7 Comm. Parameter Setting

Port

0

0

Baud rate

19200 bps

19200 bps

Parity

Even

Even

Transmission code

Data length

7

7

Stop bit

1

1

Terminating resistance

ON for RS-422