Hakko MONITOUCH V7 series User Manual

Page 194

Advertising
background image

4

1. Ethernet

4-43

Netw

or

k C

o

mm

uni
ca
tio
n

s

Get Error Contents

int HKEtn_GetLastError()

• Error codes and solutions

Code

Contents

Solution

−1

Undefined command (receive timeout)

Check the command.

−2

Undefined IP address

Check the IP address.

−3

Target station busy

Reduce the frequency of communications.

−4

Illegal packet bytes

Check response processing at the target
station.

−5

Packet bytes exceed the maximum
number.

Reduce the send packet size.

−6

Local mode error

Check that the target station is in the RUN
mode.

−7

Preparing for communications

Start communications when the target
station is ready.

−8

Communication failure

Cannot access

Check the target station.

−9

Cannot process due to short memory

Check the memory space at the target
station.

−10

Illegal received data

Check the command.

−20

Socket initialization error

Check parameters for initialization.

−50

Requested packet byte exceeds the
maximum number.

Reduce the requested size.

−51

Address error

Check the requested memory type.

−52

Communication failure

Cannot access

Check the target station.

−54

Write protected

Check write-protection of the card.

−55

Cannot process due to short memory

Check the memory space at the target
station.

−56

Sampling buffer error

Check the command.

−100 Processing another command

Continue retrying.

−101 Command control

Buffer over

Reduce the frequency of communications.

−120 Communications aborted by the user

Communications are forcedly aborted.

−121 Received during command processing

Reduce the frequency of communications.