1:n connection (multi-drop), 1:n connection, Wiring (rs-422/485) – Hakko MONITOUCH V7 series User Manual

Page 106: 1 : n connection (multi-drop) -9, 1 : n connection -9, Wiring (rs-422/485) -9, 1 : n connection (multi-drop), 1 : n connection

Advertising
background image

3

2. 1 : n Connection (Multi-drop)

3-9

Ser

ial Comm

uni
c

a

ti

ons

2.

1 : n Connection
(Multi-drop)

1 : n Connection

One V7 series is connected to multiple PLCs. (Maximum connectable PLCs: 32)

Wiring (RS-422/485)

For connecting information, refer to the instruction manual for the PLC.

Example:

The following example shows how one V7 series is connected to three PLCs made by
MITSUBISHI. For more information, refer to the MITSUBISHI’s instruction manual for
the PLC.

PLC1

PLC2

PLC3

PLCn (n=1 ~ 32)

CN1

F1

F2

F3

F4

F5

F6

F7

SYSTEM

POWER

Maximum length (V7 series to the terminating PLC) = 500 m

RS-422/RS-485 connection

V7 series

(n = 1 to 32)

FG

RDA

RDB

SDA

SDB

SG

FG

RDA

RDB

SDA

SDB

SG

FG

+SD

-SD

+RD

-RD

SG

1

12

13

24

25

7

FG

RDA

RDB

SDA

SDB

SG

* Use shielded twist-pair cables.

Signal

Pin No.

V7 (CN1)

RD terminating

resistance

(ON)

Link unit

Link unit

Link unit

Signal Signal

Terminating

resistance

(OFF)

Terminating

resistance

(OFF)

Terminating

resistance

(ON)

Signal