7. PLC2Way

Data Sampling in the PLC2 Memory

To perform data sampling in the PLC2 memory, the following settings are required.

• Temperature control network/PLC2Way table editing
• Buffering area setting
• Memory card setting (when [SRAM] or [CF Card] is selected for [Store Target] in the

[Buffering Area Setting] dialog)

• Trend sampling or data sampling setting (setting for displaying data stored in the

specified buffer)

1. Buffering area setting

Click [System Setting]

→ [Buffering Area Setting]. The [Buffering Area Setting] dialog is

opened.

[Sampling Method]

Temperature Control Net/PLC2

[No. of Table]

Select the temperature control network/PLC2Way table number for sampling.

[Sampling Time]

Specify the number of sampling times.

[Store Target] (Internal Buffer/SRAM/SF Card)

Choose the desired medium for storing sampling data.
Internal Buffer:

Stores data in the internal buffer of the V7 series. (RAM)

SRAM:

Stores data in the SRAM area. (SRAM mounted on the unit,
V7EM-S, REC-MCARD SRAM)

CF Card:

Stores data in the CF card.

[Full Processing] (Continuous/Stop)

Choose the desired processing when the target medium space has been used up.

- Continuous:

When [Sampling Time] has been exceeded, data from the oldest
is discarded.

- Stop:

When [Sampling Time] has been exceeded, sampling is stopped.