V-sft setting, V-sft setting -24, V-link setting – Hakko MONITOUCH V7 series User Manual

Page 121

Advertising
background image

3-24

6. V-Link

V-SFT Setting

The V-SFT settings required for V-Link are explained.

V-Link Setting

1. Click [System Setting]

→ [V-Link Setting].

2. The [V-Link Setting] dialog is displayed.

3. Check [

Use MJ port as V-Link] and make the setting for communications between

the V7 series and the computer.

[Refer to Modular]

Select the modular jack to be used. Modular Jack 1/Modular Jack 2

[Baud Rate]

4800 / 9600 / 19200 / 38400 / 57600 / 115 kbps

[Local Port] (1 to 31)

Set the port number of the V7 series.

[Send Delay Time] (msec)

Set a time delay in sending a response after receipt of data.

[Parity]

None/Odd/Even

[Signal Level]

RS-232C / RS-485
With RS-232C, one V7 series can be connected; with RS-485, a maximum of 31 V7
series can be connected.

[Data Length]

7-bit/8-bit

[Stop Bit]

1-bit/2-bit

[Use sum check]

Check this option when using a sum check.

[Add CR/LF]

Check this option when adding CR/LF.