1. MITSUBISHI PLC

5-5

Co
nne

c

tio

n

to P

L

Cs

QnH (A) Series CPU, QnH(Q) Series CPU

Communication parameters for the V7 series except the baud rate are automatically set.

* The maximum baud rate available with the V7 series is 115200 bps. Select the appropriate

baud rate depending on the used PLC and environment.

FX Series CPU, FX2N Series CPU, FX1S Series CPU

Communication parameters for the V7 series are automatically set.

FX Series Link (A Protocol)

*1 Select RS-485 when the link unit FX2N-485-BD, FX2N-422-BD, FX1N-485-BD, FX1N-422-BD or

FX0N-485-ADP is used.

* We recommend to set 2 ms or above for [Send Delay Time] in the [Detail] tab window of the

[Comm. Parameter] dialog of the V7 series.

Item

Setting on PLC

V7 Comm. Parameter Setting

Baud rate

19200 bps

19200 bps

Parity

Even

Even

Transmission code

Data length

7

7

Stop bit

1

1

Protocol

Special protocol communication

(fixed)

H/W type

*1

Normal/RS-232C

RS-232C

Sumcheck

Added (fixed)

Transmission mode

Mode 1

Trans. Mode 1