Opcn-1, Opcn-1 -52 – Hakko MONITOUCH V7 series User Manual

Page 203

Advertising
background image

4-52

5. OPCN-1

5.

OPCN-1

OPCN-1

• To use OPCN-1 communications on the V7 series, the communication interface unit

“CU-00” must be mounted. When the V7 series is equipped with the communication
interface unit CU-00, it becomes an OPCN-1-ready device.

• The V7 series that supports OPCN-1 communications is a programmable display that

can perform data transfer with the master station (PLC, etc.) in compliance with
“JEM-F3008 programmable controller field network standard (level 1)” (normally called
“OPCN-1”) that is determined by the Japan Electrical Manufacturers’ Association.

• The GET/PUT service is supported, and communications with the PLC can be

performed without program in the same way as communications via a link unit.

• The V7 series that supports OPCN-1 communications falls in the TYPE-S51l class.

• It is possible to perform high-speed communications by connecting multiple slave

stations to one master station (PLC).
Example: System configuration with two V7 series

• Insulated/Not insulated

I:

Insulated

U: Not insulated

• Wiring method

1: 2-wire connection
2: 3-wire connection

• Transmission range

1: 125 kbps

4: 1 Mbps

2: 250 kbps

5: All baud rates

3: 500 kbps

• Unit type

M: Master
S: Slave
A: Master/Slave

TYPE- S 5 1

I

run

PLC

V7

1

V7

2

F1

F2

F3

F4

F5

F6

F1

F2

F3

F4

F5

F6

Master station

JPCN-1
-ready product
Robot

JPCN-1
-ready product
Solenoid valve

Advertising