Idec plc, Available plcs, Communication setting – Hakko MONITOUCH V7 series User Manual

Page 325: Available memory, Idec plc -118, Available plcs -118, Communication setting -118, Available memory -118

Advertising
background image

5-118

22. IDEC PLC

22. IDEC PLC

Available PLCs

* When using RS-232C cable “FC2A-KC2” made by IDEC, connect the cable shown in [Wiring

Diagram 3] to the D-sub 9-pin side of the FC2A-KC2 cable for communications with the V7 series.

Communication Setting

The recommended communication parameter settings of the PLC and the V7 series is as follows:

Available Memory

The available memory setting range varies depending on the PLC model. Be sure to set within the
range available with the PLC to be used. Use [TYPE] when assigning the indirect memory for macro
programs.

Select PLC Type

PLC

Unit/Port

Connection

MICRO3

MICRO3

Loader port

RS-232C

IDEC cable “FC2A-KC1”
or
IDEC cable “FC2A-KC2”

*

+

[Wiring Diagram 1]

Item

Setting on PLC

V7 Comm. Parameter Setting

Baud rate

9600 bps

9600 bps

Port

1

1

Parity

Even

Even

Transmission code

Data length

7

7

Stop bit

1

1

Memory

TYPE

Remarks

D

(data register)

0

I

(input)

1

Q

(output)

2

M

(internal relay)

3

R

(shift register)

4

TS

(timer/set value)

5

TN

(timer/enumerated value)

6

T

(timer/contact)

7

Read only

CS

(counter/set value)

8

CN

(counter/enumerated value)

9

C

(counter/contact)

10

Read only

Advertising