5

11. Allen-Bradley PLC

5-73

Co
nne

c

tio

n

to P

L

Cs

Communication Setting

The recommended communication parameter settings of the PLC and the V7 series is as follows:

PLC-5 series

SLC500 series

Micro Logix 1000

Item

Setting on PLC

V7 Comm. Parameter Setting

Baud rate

19200 bps

19200 bps

Port

0

0

Parity

Even

Even

Transmission mode

RS-232C

RS-422

1785-KE not supported

Transmission code

Data length

8

8

Stop bit

1

1

Protocol

Full duplex (fixed)

Error check

BCC (fixed)

Response

NO (fixed)

Item

Setting on PLC

V7 Comm. Parameter Setting

Baud rate

19200 bps

19200 bps

Port

0

0

Parity

Even

Even

Transmission mode

RS-232C

RS-422

Channel 0 not supported

Transmission code

Data length

8

8

Stop bit

1

1

Protocol

Full duplex (fixed)

Error check

BCC (fixed)

Response

NO (fixed)

Item

Setting on PLC

V7 Comm. Parameter Setting

Baud rate

9600 bps

9600 bps

Port

0

0

Parity

None (fixed)

Not provided

Transmission code

Data length

8 (fixed)

8

Stop bit

1 (fixed)

1

Error check

CRC (fixed)

Advertising