Jw series: link unit switch setting, Jw series: link unit switch setting -31 – Hakko MONITOUCH V7 series User Manual

Page 238

Advertising
background image

5

3. SHARP PLC

5-31

Co
nne

c

tio

n

to P

L

Cs

JW Series: Link Unit Switch Setting

Baud Rate: 19200 bps

JW100/70H COM Port, JW20 COM Port:
System Memory Setting

The settings for communications with the V7 series should be made at the system memory as shown
below.

• JW-70CU/100CU, JW70CUH/100CUH, JW22CU

• JW-32CUH/33CUH

- Communication port 1

- Communication port 2

Switch

Setting

Contents

SW0

4

Command mode

SW1

1

Station address (lower half)

SW2

0

Station address (upper half)

SW3-1

OFF

Not used

SW3-2

ON

4-wire system

SW3-3

OFF

Not used

SW3-4

ON

Even parity

SW4

0

Baud rate
0: 19200

1: 9600

2: 4800

3: 2400

4: 1200

5: 600

SW7

ON

Terminating resistance provided

System Memory

Setting

Contents

#236

30H

Stop bit: 2 bits, parity: even, baud rate: 192000

#237

01H

Port

System Memory

Setting

Contents

#234

30H

Stop bit: 2 bits, parity: even, baud rate: 192000

#235

01H

Port

System Memory

Setting

Contents

#236

30H

Stop bit: 2 bits, parity: even, baud rate: 192000

#237

01H

Port