3. Errors Displayed on the V7 Series

Error Messages for Network Communication

• Ethernet

• MELSECNET/10

• CC-LINK

Error Message

Contents

Solution

Ethernet Error: XXXX

The Ethernet status is saved at system
memory address $s518 and a code other
than “0” (normal) is received.
XXXX: Error No.

For the contents and solution to each
error number, refer to “Chapter 4
Network Communications/
Error Display.

Error Message

Contents

Solution

I/F Board Err

The I/F unit for NET/10 has an error.

Contact your local distributor.

Request Code Err

The request command from NET/10 has
an error.

Request Data Err

The request data from NET/10 has an
error.

Word Writing to Sp. Relay
(MITSUBISHI: A Series)

Word writing to a special relay (M9000
and later) is attempted.
(Notes: Only bit writing is possible for
special relays when connecting with
NET/10.)

Do not attempt to perform word writing to
special relays.

Error Message

Contents

Solution

I/F Board Err

The I/F unit for CC-LINK has an error.

Contact your local distributor.

No. of Occupy Setting Err

The number of occupy in [Comm.
Parameter] is different from the number
of occupy by switches.

Check the setting of the number of
occupy.

Network I/O Access Err

MONITOUCH is about to access
exceeding the set number of input/output
words.

Check the memory for the network I/O in
the screen data file.

Station Number Err

The port number set by a switch is not
within the setting range (1 to 64).

Specify the port number within the setting
range.

Word Writing to Sp. Relay

Word writing to a special relay (M9000
and later) is attempted.
(Notes: Only bit writing is possible for
special relays when connecting with
CC-LINK.)

Do not attempt to perform word writing to
special relays.