N:1 connection (multi-link 2), Multi-link 2, N : 1 connection (multi-link 2) -11 – Hakko MONITOUCH V7 series User Manual

Page 108: Multi-link 2 -11, N : 1 connection (multi-link 2)

Advertising
background image

3

3. n : 1 Connection (Multi-link 2)

3-11

Ser

ial Comm

uni
c

a

ti

ons

3.

n : 1 Connection
(Multi-link 2)

Multi-link 2

• One PLC is connected to a maximum of four V7 series.

• An original network is created where the V7 series (Local Port 1) that is directly

connected to the PLC is the master station, and other three V7 series are slave
stations. Only the master station makes communications directly with the PLC, and the
slave stations make communications with the PLC via the master station.

• Communications between the V7 master station and the PLC depend on the

communication speed set on the PLC. The maximum available speed for the V7 series
is 115 kbps, which is higher than the one available with multi-link connection described
in “4. n : 1 Connection (Multi-link).”

• This multi-link connection is available with almost all the PLC models that support 1 : 1

connection (refer to the Appendix). The connection between the master station and the
PLC is the same as the one for 1 : 1 connection).

• Use the RS-485 2-wire connection between stations of the V7 series. Please use

Hakko Electronics’ multi-link 2 master cable (V6-MLT) for connection between the
master station (Local Port 1) and the slave station (Local Port 2).

• In the following cases, multi-link 2 connection is not available.

1. A communication interface unit (example: OPCN-1, CC-LINK, Ethernet, etc) is

used.

2. The V7 series (master or slave station) is used for the temperature control network

or PLC2Way function.

PLC

RS-232C
RS-422
RS-485

CN1

MJ2

CN1

CN1

CN1

F1

F2

F3

F4

F5

F6

F7

SYSTEM

POWER

F1

F2

F3

F4

F5

F6

F7

SYSTEM

POWER

F1

F2

F3

F4

F5

F6

F7

SYSTEM

POWER

F1

F2

F3

F4

F5

F6

F7

SYSTEM

POWER

Hakko Electronics’ cable
“V6-MLT” (3 m)

RS-485 connection

V7 master station

V7 slave station

V7 slave station

Local Port 1

Local Port 2

Local Port 3

Local Port 4

V7 slave station

Advertising