3

7. PLC2Way

3-43

Ser

ial Comm

uni
c

a

ti

ons

• Calculating the buffering area capacity

When [Internal Buffer] is selected for [Store Target] in the [Buffering Area Setting],
the maximum available capacity is 32K words. When [Temp Control Net/PLC2] is
selected for [Sampling Method], the required capacity can be calculated as shown
below.

1 sample = [Words*] + 2 words
Buffer size = [Sampling Times]

× 1 sample

* [Words] here means the number of words in the memory addresses used in the

temperature control network/PLC2Way table that is set for [No. of Table].

2. Memory card setting

When [SRAM] or [CF Card] is selected for [Store Target] in the [Buffering Area Setting]
dialog, the memory card setting is required.

* The used memory capacity of SRAM and CF card can be calculated in the same way as

the buffering area.

1) Click [System Setting]

→ [Memory Card Setting]. The [Memory Card] dialog is

opened.

2) Select [Buffering File] for [Type].

3) Match the file number (tab) in the [Memory Card] dialog with [Output File No.] in the

[Buffering Area Setting] dialog.

Select the tab of the same number.