Hakko MONITOUCH V7 series User Manual

Page 116

Advertising
background image

3

4. n : 1 Connection (Multi-link)

3-19

Ser

ial Comm

uni
c

a

ti

ons

[Total] (2 to 32)

Set the total number of the V7 series included in the connection.

[Retry Cycle] (

×10)

When the V7 series has a problem, it is temporarily removed from the
communication targets, and the master station sends an inquiry for restoration every
number of cycles specified for [Retry Cycle]. This setting does not affect the
communication speed if no problem is occurring; however, if there is any problem, it
does affect the communication speed.

• When the setting value is small: It will not take a long time before restoration.
• When the setting value is large: It will take a longer time before restoration.

* For [Send Delay Time], [Total] and [Retry Cycle], the same values must be set on all the V7

series that are connected in the same communication line.

Supplemental Information:

[Retrials] in the [Detail] tab window of the [Comm.
Parameter] dialog is the number of retrials that the
V7 series sends an inquiry to the PLC.