7. Mounting Procedure

7.

Mounting Procedure

Mounting Procedure

1. Cut out the mounting panel (max. thick: 5 mm) to match the dimensions shown below.

2. Insert four fixtures attached to the V7 series into the mounting holes, and tighten them

with the locking screws.
Tightening torque

V708/V708i/V710/V710i: 0.3 to 0.5 N•m
V712/V712i:

0.5 to 0.7 N•m

* When the V7 unit is attached to the

mounting panel, the fixtures and frame
grounds (FG) are connected. To prevent
static electricity, be sure to connect the
mounting panel to the frame ground.

3. Mount the gasket in contact with the mounting panel so that it will be sandwiched

securely between the unit and the mounting plate.

Mounting Angle

Install the unit within the angle of 15

° to 135° degrees as

shown on the right.

165.5

220.5

+

0.5

0

0

+

0.5

246.2

313

V712/V712i

V708/V708i

216.2

289

+

0.5

0

0

+

0.5

V710/V710i

+

0.5

0

0

+

0.5

F1

F2

F3

F4

F5

F6

F7

SYS

TEM

POW

ER

216.2

289

+0.5

0

0

0.5

Mounting panel

Panel cut-out hole

• Panel cut-out dimensions

(Unit: mm)

MJ1

MJ2

PRIN

TER

CF

CN5

MEM

ORY

CN6

LAN

CN1

100-

240V

AC

L

N

Fixtures

Mounting hole

Mounting hole

V7 series

Mounting panel

Fixtures

17.8

10.5

30.0

Fixture dimensions

(Unit: mm)