9. FUJI PLC

9.

FUJI PLC

Available PLCs

*1 To use FLEX-PC of Toyota version, select [FLEX-PC (T)].
*2 To use FLEX-PC CPU of Toyota version, select [FLEX-PC CPU (T)].

Communication Setting

The recommended communication parameter settings of the PLC and the V7 series is as follows:

MICREX-F Series, FLEX-PC Series

Select PLC Type

PLC

Unit/Port

Connection

PLC2Way

MICREX-F series

(MICREX-F series V4)

F55

NV1L-RS2

RS-232C [Wiring Diagram 1]

F70, F70S

NC1L-RS2

RS-232C [Wiring Diagram 1]

NC1L-RS4

RS-485

[Wiring Diagram 3]

F80H, F120H,
F120S F140S,
F15

S

FFU120B

RS-232C [Wiring Diagram 1]

FFK120A

RS-485

[Wiring Diagram 3]

FLEX-PC series

*1

NS-T

NJRS-1

RS-232C [Wiring Diagram 1]

NJ-T

NJRS-2

RS-232C [Wiring Diagram 1]

NJRS-4

RS-485

[Wiring Diagram 3]

FLEX-PC CPU

*2

FLEX-PC

CPU port

RS-485

Hakko Electronics’
cable “FU-CPUNS”

NJ-B16

RS-232C port

RS-232C [Wiring Diagram 2]

FLEX-PC COM (T)

FLEX-PC NJ-JM

Computer link
terminal block

RS-422

[Wiring Diagram 4]

Item

Setting on PLC

V7 Comm. Parameter Setting

Baud rate

19200 bps

19200 bps

Port

0

0

Parity

Even

Even

Transmission mode

RS-232C

1 (asynchronous non-protocol by

command) (fixed)

RS-422

3 (asynchronous non-protocol by

command) (fixed)

Transmission code

Data length

7 (ASCII)

7

Stop bit

1

1

Terminating resistance at receiver

Provided for RS-485