Serial connector (cn1), Serial connector for plc connection, Serial connector (cn1) -28 – Hakko MONITOUCH V7 series User Manual

Page 45: Serial connector for plc connection -28

Advertising
background image

1-28

11. Serial Connector (CN1)

11. Serial Connector (CN1)

Serial Connector for PLC Connection

1. To communicate with the PLC (RS-232C, RS-422/485), connect the cable to the serial

connector (CN1) at the bottom of the V7 unit.

- For V708/V708i:

- For V710/V710i/V712/V712i:

2. The serial connector pins correspond to signals as given below.

3. The following connector is recommended.

DDK-make 17JE23250-02 (D8A)

D-sub 25-pin, female, metric thread, with hood

Bottom View

Bottom View

CN1 (D-sub 25-pin, female)

Pin No.

Signal Name

Contents

1

FG

Frame ground

2

SD

RS-232C send data

3

RD

RS-232C receive data

4

RS

RS-232C request to send

5

CS

RS-232C clear to send

6

Not used

7

SG

Signal ground

8

Not used

9

+5V

Use prohibited

10

0V

Use prohibited

11

Not used

12

+SD

RS-422 send data (+)

13

−SD

RS-422 send data (

−)

14

+RS

RS-422 RS send data (+)

15

Not used

16

Not used

17

−RS

RS-422 RS send data (

−)

18

−CS

RS-422 CS receive data (

−)

19

+CS

RS-422 CS receive data (+)

20

Not used

21

Use prohibited (V708: not used)

22

Use prohibited (V708: not used)

23

Not used

24

+RD

RS-422 receive data (+)

25

−RD

RS-422 receive data (

−)

1

14

13

25

Advertising