Oxymitter 4000

Figure 8-11. Fault 9, High Heater Temp

Fault 9, High Heater Temp

Figure 8-11 shows the electronic assembly for an
Oxymitter 4000 with a membrane keypad (upper
view) and an Oxymitter 4000 with an LOI (lower
view).

Membrane Keypad

When Fault 9 is detected, the HEATER LED
flashes five times, pauses for three seconds, and
repeats.

1. If the thermocouple produces a voltage in

excess of approximately 30.7 mV, the high
heater temp alarm activates.

2. The 4-20 mA signal returns to the default

value (4 or 20 mA).

3. This alarm is self-clearing. When

temperature control is restored and the
thermocouple voltage returns to the normal
range, the alarm clears.

4. If the temperature continues to rise, the

next alarm will be the High High Heater
Temp alarm.

LOI

When Fault 9 is detected, the LOI displays the
"O2 Temp Hi" message. Refer to the comments
and procedures in paragraphs 1 through 4
above.

37260027

LOI

KEYPAD

DIAGNOSTIC

ALARMS

TEST

POINTS

HEATER T/C

HEATER

O2 CELL

CALIBRATION

CALIBRATION RECOMMENDED

O2 CELL mV +

O2 CELL mv -

HEATER T/C +

HEATER T/C -

INC

INC

DEC

DEC

HIGH

GAS

LOW

GAS

CAL

TEST GAS +

PROCESS -

% O2

SW2

TP1

J1

TP2

TP3

RED

YEL

GRN

ORG

TP4

TP5

TP6

ON

Alarms

O2 Temp Hi