Of the ten modes in Table 4-1, mode 1 through mode 7 are the alarm modes.
The factory default is mode 5 for Oxymitter 4000 units without an IMPS 4000
or SPS 4001B. In this mode, the output will signal when a unit alarm or a
CALIBRATION RECOMMENDED indication occurs.

Calibration Handshake Signal

If using an optional IMPS 4000 or SPS 4001B, the logic I/O must be
configured for calibration handshaking. Of the ten modes in Table 4-1, only
modes 8 and 9 are configured for calibration handshaking. For an Oxymitter
4000 with an IMPS 4000 or an SPS 4001B, the factory sets the default to
mode 8. In this mode, the logic I/O will be used to communicate between the
Oxymitter 4000 and the sequencer and to signal the sequencer when a
CALIBRATION RECOMMENDED indication occurs.

Table 4-1. Logic I/O

Configuration (as set at

HART/AMS or LOI)

*The default condition for an Oxymitter 4000 without an IMPS 4000 or SPS 4001B.

**The default condition for an Oxymitter 4000 with an IMPS 4000 or SPS 4001B.

Mode

Configuration

0

The unit is not configured for any alarm condition.

1

The unit is configured for a Unit Alarm.

2

The unit is configured for Low O

2

.

3

The unit is configured for both a Unit Alarm and Low O

2

.

4

The unit is configured for a High AC Impedance/CALIBRATION
RECOMMENDED.

5*

The unit is configured for both a Unit Alarm and a High AC
Impedance/CALIBRATION RECOMMENDED.

6

The unit is configured for both a Low O

2

and High AC Impedance/CALIBRATION

RECOMMENDED.

7

The unit is configured for a Unit Alarm, a Low O

2

, and a High AC

Impedance/CALIBRATION RECOMMENDED.

8**

The unit is configured for a calibration handshake with IMPS 4000 or SPS 4001B.
CALIBRATION RECOMMENDED will initiate the calibration cycle.

9

The unit is configured for a calibration handshake. CALIBRATION
RECOMMENDED will not initiate the calibration cycle with the IMPS 4000 or SPS
4001B.