Using an AGS Module: Operation

Auto Gen Start
Gen Ready 0.0Hrs
28.8VDC TS Open
P3 AGS Home

Inverting
Gen Ready

24.0VDC 12.0ADC
ALL System Home

System Home Screen – to access, press

and hold METER button for 3 sec

PORT

SETUP

04A Gen Run DC Volts
Start=23.0V/120secs
Stop =28.8V/120secs
P3 View AGS SETUP

Press PORT button until port# to

which AGS is connected appears

(i.e., AGS Home Screen)

Press SETUP button to access AGS

menus

Note: The AGS-N SETUP menus are accessed via the System Home screen and PORT button; or, by

pressing the SETUP button and rotating to the 04 AGS Setup menu, and then pressing the SELECT

knob. Refer to the procedures below to access these menu items via the AGS Home screen.

R

SETUP

Set Gen Run DC Volts
Start Volts = 23.0V
Stop Volts = 28.8V
P3 edit AGS SETUP

Set VDC Delay Times
Start Delay=120secs
Stop Delay =120secs
P3 edit AGS SETUP

04A Gen Run DC Volts
Start=23.0V/120secs
Stop =28.8V/120secs

P3 View AGS SETUP

04B Gen Run Time
OFF

P3 View AGS SETUP

Set Gen Run Time
Start Daily= OFF
Stop Daily =12:00AM
P3 edit AGS SETUP

04C Gen Run AC Amps
OFF

P3 View AGS SETUP

P

P

Start=OFF, 18.0-32.0
Stop=18.2-32.0, Float

R

P

OFF, 12:00AM-11:45PM

R

Set Gen Run AC Amps
Start AC Amps = OFF
Stop AC Amps = 4A

P3 edit AGS SETUP

P

Set Amps Delay Time
Start Delay=120secs
Stop Delay =120secs

P3 edit AGS SETUP

P

OFF, 4-60

0-127secs, 1-127mins

0-127secs, 1-127mins

Set Gen Run SOC
Start SOC = OFF
Stop SOC = 95%
P3 edit AGS SETUP

04D Gen Run SOC
OFF

P3 View AGS SETUP

04E Gen Run Temp
OFF

P3 View AGS SETUP

Set Gen Run Temp
Start Temp= OFF

P3 edit AGS SETUP

04F Max Gen Run Time
when Autostarted
= 12.0 Hours
P3 View AGS SETUP

P

R

P

R

Set Max Gen Run Time
when Autostarted
= 12.0 Hours

P3 edit AGS SETUP

P

OFF, 0.1-25.5

Start = OFF, ExtInput, 65F-95F
Run
= 0.5-25.5 Hrs*

R

Start = OFF, 20-99%
Stop
= 21-100%

x2

x2

* Shows if a start

temp selected

Figure 7-3, AGS SETUP Menu Maps (Section 1)