Page 76

Using an AGS Module

04D Gen Run SOC
Start SOC = 50%
Stop SOC = 95%
P3 View AGS SETUP

PORT, CTRL,

METER, SETUP,

and TECH Buttons

PORT

CTRL

METER

SETUP

TECH

Figure 7-1, ME-RTR’s AGS Confi guration Access Buttons

7.0 Using an AGS Module

The AGS-N menus in the ME-RTR router under the CTRL, METER, SETUP, and TECH buttons allow

you to customize and monitor operating parameters, and to help troubleshoot your autostart/

autostop generator system. To confi gure and use the AGS with the ME-RTR, refer to the mini-index

below to direct you to the appropriate section.
7.1

ME-AGS-N Setup (with the ME-RTR)

page 79

7.2

ME-AGS-N Operation/Monitoring (with the ME-RTR)

page 92

7.3

ME-AGS-N Router Troubleshooting (with the ME-RTR)

page 103

IMPORTANT: The AGS must be a network version (ME-AGS-N) and must be connected and

communicating with the ME-RTR in order to set up and/or control the AGS. If the AGS is not

communicating, “No AGS Present” appears when accessing the SETUP/04 AGS Setup or the

CTRL/03 Gen Control menus, unless the TECH: 07 Show all Menus menu has been set to “Yes”.

Refer to Section 3.3.5 for more info on the TECH: 07 menu.

Info: Even though you can connect a ME-ARC remote control to the ME-RTR and activate

the AGS (through the FAVS button), all the AGS’s autostart/autostop settings must be

set up in the ME-RTR.
Info: The Auto Connect setting must be selected if a ME-AGS-N is installed and enabled

in the system. Otherwise, when the generator is autostarted, it may be prevented from

connecting because the criteria to allow the AC input to connect (AC In based on time,

VDC, or SOC) may not have been met.
Note: This is true unless you are using an inverter that has two independent AC

inputs—one for grid and the other for generator (i.e., MSH4024RE). On the MSH4024RE

inverter, the AC In Control features only work with the GRID IN (AC1) input.

7.0.1

Software Differences Between AGS Versions

Even though the router provides a selection/feature or shows a setting, based on the version of

your ME-AGS-N, this selection or setting may not be available. Use Table 7-1 to determine if your

ME-AGS-N is compatible with the selection or setting you want to use.

Info: Refer to TECH/02 Port Vers (or TECH/03 AccPort Versions)—depending on what

port the AGS is connected—to determine the software version in your AGS.