Magnum Energy ME-RTR Router User Manual

Page 87

Advertising
background image

Page 79

©

2014 Magnum Energy, Inc.

Using an AGS Module: Setup

• Set VDC Delay Times (Start Delay) This setting determines how long the Set Gen Run

DC Volts (Start Volts) parameter must be continuously maintained before autostarting the

generator. This ensures the generator does not nuisance start. By setting a delay, momentary

surges from heavy loads—that can cause the battery voltage to dip—will not start the generator

unnecessarily.

Default setting: Start Delay = 120secs
Range: 0-127 Seconds, then 1-127 Minutes

Where should I set Start Delay? First, determine what loads will be running when the generator

needs to start. The larger the load the shorter the delay time setting. When a large load is applied

to the battery bank the battery voltage will drop quickly, so the delay time should be short to

ensure the batteries are not over-discharged. If you are not sure what loads might be running or

where to set the start time delay, error on the side of setting a shorter time such as the default

of 2 minutes (to protect batteries from over-discharge).

SETUP: 04A Gen Run DC Volts Menu
This menu provides the option to start the generator when the battery voltage gets low, and to

stop the generator either when the battery reaches a higher voltage level, or when the battery

has been fully charged and goes into the Float Charge stage. Using voltage is the most common

method of automatically starting and stopping the generator because it is considered the simplest

and easiest to understand. The 04A Gen Run DC Volts menu also has start and stop delay settings

that minimize nuisance starts/stops to prevent short cycle run times of the generator.
• Set Gen Run DC Volts (Start Volts) – This setting will start the generator when the battery

voltage (on Terminals #3 & #4 of the AGS) decreases to or below this setting continuously for

the duration of the Set VDC Delay Times (Start Delay) setting.

Default settings: Start Volts = 11.5 VDC (12v), 23.0 VDC (24v), 46.0 VDC (48v)
Ranges: OFF, 9.0-15.9 VDC (12v), 18.0-31.8 VDC (24v), 36.0-63.6 VDC (48v)

Where should I set Start Volts? The VDC start voltage must be high enough to not over-

discharge the battery, but low enough to keep from nuisance starting the generator. Typically,

the start volts setting is set based on what is determined to be approximately 50% of the battery

capacity. Since this is an inverter/battery system, and the battery is normally loaded, the VDC

used to determine 50% battery capacity should be set lower than what is shown on typical

battery voltage SOC charts (approximately 11-11.5 in a 12-volt system), which show the battery

at rest (unloaded). A typical start voltage setting would be between 11.0 VDC-11.5 VDC for a

12-volt system.

Info:

The Gen Run DC Volts feature uses the voltage as shown on the METER button’s

04B DC Volts to AGS menu to determine when to autostart and autostop the generator.

Info: Using a 12-volt battery as an example, a typical SOC (State of Charge) battery

chart will show that 12.2 VDC is considered 50% SOC. This voltage is a battery “at

rest,” meaning it has no load connected and has been at rest for a minimum of 30 min.

While this voltage is accurate under these at rest conditions, this same voltage with a

load applied means the battery is well above 50% SOC, and should be set much lower.

However, the larger the battery bank the less the voltage will be affected by a load

applied to the battery bank.
Info: When using the 04A Gen Run DC Volts feature, ensure the Set Gen Run DC Volts

(Start Volts) setting is higher than the 02B Low Battery Cut Out (LBCO) Volts setting

(under SETUP/02 Inverter Setup). This prevents the inverter from shutting down before

the generator comes on. The 04A Gen Run DC Volts setting should be high enough to

allow suffi cient time until the generator is allowed to start (i.e., start delay time) and

the inverter is allowed to connect (i.e., warm-up time and AC input delay time). Set

the Set Gen Run DC Volts (Start Volts) setting at least 1-volt higher than the inverter’s

LBCO setting, and then adjust depending on how long it takes the battery voltage to fall

under normal usage conditions.

Advertising