Page 63

©

2014 Magnum Energy, Inc.

Operation

Reminder to EQ – This display indicates that it is time to EQ your batteries. This occurs when

the SETUP: 03G Days to remind when to EQ setting has been enabled and the # of days has been

exceeded.

Info: The Reminder to EQ display is reset by initiating an EQ charge cycle, or by turning

the SETUP: 03G Days to remind when to EQ setting to OFF.

Reminder to EQ appears on LCD. PWR (green) LED

is on solid and CHG (green) LED blinks.

FAULT

PWR

CHG

INV

Reminder to EQ

Settings/Info...

Figure 5-25, Reminder to EQ Mode

SOC Connect appears on LCD. PWR (green) LED is on

solid and CHG (green) LED is blinking.

FAULT

PWR

CHG

INV

SOC Connect

Settings/Info...

Figure 5-26, SOC Connect Mode

SOC Connect – AC power is present at the inverter’s AC input, but not allowed to connect.

The battery bank’s State of Charge needs to reach the Connect SOC setting from the SETUP: 02E

AC In – SOC menu in order for the inverter/charger to connect to the incoming AC.

Time Connect appears on LCD. PWR (green) LED is

on solid and CHG (green) LED blinks.

Time Connect – AC power is present at the inverter’s AC input, but not allowed to connect.

The time of day needs to fall within the Connect time and the Disconnect time settings per the

SETUP: 02C AC In – Time menu in order for the inverter/charger to connect to the incoming AC.

FAULT

PWR

CHG

INV

Time Connect

Settings/Info...

Figure 5-27, Time Connect Mode

FAULT

PWR

CHG

INV

VDC Connect

Settings/Info...

VDC Connect appears on LCD. PWR (green) LED is on

solid and CHG (green) LED blinks.

VDC Connect – AC power is present at the inverter’s AC input, but not allowed to connect.

The battery voltage needs to fall below the Connect volts setting from the SETUP: 02D AC In –

Volts DC menu in order for the inverter/charger to connect to the incoming AC.

Figure 5-28, VDC Connect Mode