Why would I use Gen Run AC Amps? This feature is designed to prevent the battery from being

heavily discharged by monitoring the battery current used to power the inverter loads (shown in AC

amps). When the AC current exceeds the Start AC Amps setting, a generator autostart is initiated.

After the generator connects to the inverter, the current from the generator is now used to run the

loads instead of the battery current. This feature is useful when there is occasionally a large load

or combinations of loads that the inverter is able to run, but by doing so would quickly deplete

the battery bank. Typically, these large loads might be motors, well pumps, A/C units, or freezers.

Info: The 04C Gen Run AC Amps feature is not designed to turn on the generator to

power loads above the capacity of the inverter. If attempting to run loads above the

inverter capacity, the inverter may overload and shut down before the generator can

autostart and power the heavy load thru the inverter.

Where should I set Gen Run AC Amps? Typically, the generator should autostart when the

AC load amps is >70-75% of the inverter AC current output rating¹. This keeps the inverter from

running too large a load and also keeps the batteries from cycling unnecessarily. Set Stop AC

Amps just below the start amps to ensure the large load has turned off. Set the start delay time

so surge loads don’t trigger a false start, and the stop delay time is long enough to ensure the

load has turned off.
Example: In this scenario, most AC loads typically do not exceed 20A when in Inverter mode.

When a freezer or well pump starts, the load exceeds 30A so the battery voltage starts to quickly

drop. Instead of cycling the batteries to a low voltage, set Start AC Amps to 25A with a 60-second

delay (using Start Delay setting). Set the Stop AC Amps menu to 20A with a 60-second delay

(using Stop Delay setting). After 60 seconds of detecting a larger than 25A load on the inverter,

the generator autostarts and powers the loads and recharges the batteries. Once the AC amps

load drops below 20A for 60 seconds, the gen turns off.
SETUP: 04D Gen Run SOC Menu
This menu starts and stops the generator based on the SOC (State of Charge) reading from the

attached battery monitor, as shown on the METER button’s 05A BMK SOC display. This is the

best method for using AGS settings to start/stop your generator. Since the ME-BMK already uses

voltage, time, and current to determine the true SOC of the batteries, there is little guesswork or

calculating needed to determine what settings to use.
• Set Gen Run SOC (Start SOC) – This menu sets the SOC level for autostarting the generator.

Default setting: Start SOC = OFF
Range: OFF, 20%-99%

• Set Gen Run SOC (Stop SOC) – This menu sets the SOC level for autostopping the generator.

Default setting: Stop SOC = 90%
Range: 21%-100%

Info: There is no start or stop delay time needed since the ME-BMK already displays an

accurate state of charge of the batteries.

Info: The optional Battery Monitor Kit (ME-BMK or ME-BMK-NS) must be installed and

enabled to use the 04D Gen Run SOC autostart/autostop feature.

Info: When using the 04D Gen Run SOC autostart/autostop feature, the generator

autostarts and runs until the battery bank has reached the Stop SOC setting or the

AGS’s SETUP: 04F Max Gen Run Time setting is reached, whichever occurs fi rst. Ensure

the charger never leaves the Bulk/Absorption charge mode. This is done by ensuring

the SETUP: 03 Absorb Done selection is “SOC” and the setting is greater than or equal

to the Stop SOC setting; and either set the Max Gen Run Time setting to OFF, or set it

long enough to ensure the generator is able to run until the battery is fully charged. If

the charger is allowed to exit the Bulk/Absorption charge mode (i.e., go to Float/Silent),

the battery SOC may never reach 100%.

Note¹For a 4000 watt inverter, this would mean setting Start AC Amps at 25A.