Magnum Energy ME-RTR Router User Manual

Page 73

Advertising
background image

Page 65

©

2014 Magnum Energy, Inc.

Operation

Breaker Tripped appears on the LCD and the FAULT

(red) LED is on. The PWR (green), CHG (green), and

INV (green) LEDs are off.

• Breaker Tripped (Brk Trip) – The AC input breaker on the inverter/charger has opened due

to excess current fl ow through the inverter to the AC loads.

Remedy: After reducing the AC loads on the inverter’s output, push in the inverter’s AC

input circuit breaker to reset and resume operation.

FAULT

PWR

CHG

INV

Breaker Tripped

Settings/Info...

Figure 5-31, Breaker Tripped Fault

Dead Batt Charge appears on the LCD and the FAULT (red)

LED is on. The PWR (green), CHG (green), and INV (green)

LEDs are off.

• Dead Battery Charge (DeadBatt) – This fault indicates a discharged battery bank, or the

battery bank is disconnected from the inverter. The unit is attempting to enter Charge mode, but

has detected less than 7 volts (12-volt models), 14 volts (for 24-volt models) or 28 volts (for 48-

volt models) on the battery bank. This fault continues until current is able to fl ow into the battery

from the battery charger. Once this happens, the fault will automatically reset.

Remedy: Remove all incoming AC to the inverter’s input, then check DC voltage on

the inverter’s DC terminals and compare it with the DC voltage on the battery bank.

These two voltages should be very close (<0.5 VDC difference). If not, check to ensure

all connections are tight and the fuse/circuit breaker between the inverter and battery

bank is good.

Figure 5-32, Dead Battery Charge Fault

FAULT

PWR

CHG

INV

Dead Batt Charge

Settings/Info...

FET Overload appears on the LCD and the FAULT (red)

LED is on. The PWR (green), CHG (green), and INV

(green) LEDs are off.

• FET Overload (FETOverL) This fault message indicates the inverter/charger has shut

down because the internal FETs (Field Effect Transistors) have quickly exceeded a safe operating

temperature. When the FETs cool, the unit requires a manual restart to resume operation.

Remedy: If the fault continues, disconnect all AC power to the inverter’s input, remove

the inverter’s AC output wires and reset the inverter (see Section 6.2). After the reset,

turn the inverter on. If the fault does not clear after the reset, the inverter may require

service.

FAULT

PWR

CHG

INV

FET Overload

Settings/Info...

Figure 5-33, FET Overload Fault

Advertising