Operation

FAULT

PWR

CHG

INV

Constant Current

Settings/Info...

Constant Current appears on LCD. PWR (green) and

CHG (green) LEDs are on solid. FAULT (red) LED is off,

and INV (green) LED could be on or off.

Figure 5-14, Constant Current Mode

• Constant

Current

(CCurrent) – The battery charger is delivering maximum current to the

batteries (determined by the Max Charge Amps setting under the SETUP button’s 03C Battery

Type: CC/CV menu). The charger will remain in Constant Current charge until the CV Charge Volts

or Max CC/CV Charge Time is reached (determined by the settings under the SETUP button’s 03C

Battery Type: CC/CV menu).
Note: This status only displays if “CC/CV” has been selected from the SETUP button’s 03C Battery

Type menu.

Constant Voltage appears on LCD. PWR (green) and

CHG (green) LEDs are on solid. FAULT (red) LED is off,

and INV (green) LED could be on or off.

FAULT

PWR

CHG

INV

Constant Voltage

Settings/Info...

Figure 5-15, Constant Voltage Mode

• Constant Voltage (CVoltage) – This mode begins when the CV Ch Volts is reached (determined

by the settings under the SETUP button’s 03C Battery Type: CC/CV menu) while in the Constant

Current charge mode. During this stage, the DC charging current decreases in order to maintain

the absorb voltage setting. This charge stage continues until the 03D Absorb Done (Time, Amps,

or SOC) or 03E Max Charge: Time setting is reached.
Note: This status only displays if “CC/CV” has been selected from the SETUP button’s 03C Battery

Type menu.

Equalizing appears on LCD. PWR (green) and CHG

(green) LEDs are on solid. FAULT (red) LED is off, and

INV (green) LED could be on or off.

• Equalizing

(Equalize)

– This display indicates the charger is delivering the equalize voltage

to the batteries based on the equalize voltage from Table 3-1 for your battery type.
Equalize charging can be enabled by the ON/OFF CHARGER button—if the SETUP button’s 03C

Battery Type setting allows. Equalization charging can only be enabled while the charger is in

Float Charge, Full Charge, or Silent Charge mode. To turn on Equalize charging, ensure the LCD

display reads “Float Charging”, “Full Charge” or “Silent”, and then press and hold down the ON/

OFF CHARGER button (about 5 seconds) until the LCD screen displays “Equalizing”.
The Equalize charge continues for four hours and then automatically stops and returns to the

previous charge mode. The Equalize charge can be manually stopped by pressing and holding

down the ON/OFF CHARGER button (about 5 seconds) until the LCD screen leaves “Equalizing”

and then leaves “Charger Standby” and shows the previous charge mode (i.e., Float Charge, Full

Charge, or Silent Charge mode).

WARNING: Equalizing produces hydrogen and oxygen gas. To avoid explosions, ensure

the battery compartment has adequate ventilation in order to dissipate this gas.

FAULT

PWR

CHG

INV

Equalizing

Settings/Info...

Figure 5-16, Equalizing Mode