4 setup button and menus – Magnum Energy ME-RTR Router User Manual

Page 31

Advertising
background image

Page 23

©

2014 Magnum Energy, Inc.

Setup

3.3.4

SETUP Button and Menus

Pressing the SETUP button provides access to the menu items and settings that enable you to

confi gure the router display, the inverter/charger, a ME-AGS-N, and a ME-BMK. Review each menu

item to determine if you need to adjust any settings to meet your system requirements.

Info: The fi rst screen that may appear when the SETUP button is pushed is a password

screen. If the PIN has been set under the TECH button’s 05 SETUP PIN menu, the fi rst

screen is the Set SETUP PIN menu. The proper PIN must now be entered in order to

access the SETUP menus. After fi ve minutes from the last button push, the display

automatically returns to the System Home screen and the PIN must be reentered in

order to access the SETUP menus. Refer to the TECH button’s SETUP PIN menu to set

or change the PIN number.

Press

SETUP

Rotate to desired selection:

Press to

select

Top line shows menu

Bottom line shows menu

(Ex: Inverter Setup menu)

01 System Setup
02 Inverter Setup
03 Charger Setup
ALL Select SETUP

02B Low Battery Cut
Out (LBCO) Volts =
20.0 Volts
ALL View INV SETUP

01 System Setup
02 Inverter Setup
03 Charger Setup
04 AGS Setup
05 BMK Setup
06 RC Setup

Figure 3-11, SETUP Button

SETUP: 01 System Setup
The following menus are used to set up the router clock and screen.
• 01A System Clock: The router contains a real time clock that must be set for proper operation

of some features. These features are: the SETUP button’s 02C AC In – Time, 04B Gen Run

Time, 04G Gen Quiet Time, 04H Gen Exercise menus, and the TECH button’s 04 Fault History

menu items.

**IMPORTANT**

It is very important that you set the time clock as it is a critical piece in effectively addressing

fault issues, as well as for the proper start/stop functions of your AGS device, if installed.

Info: The clock obtains power from the inverter and will reset if the router is disconnected

from the inverter.

To Set the Current Time
From the Set System Clock menu:
1. Rotate the SELECT knob to the hour of day, and then press SELECT.
2. Rotate the SELECT knob to the correct minute setting, and then press SELECT.
3. Rotate the SELECT knob to the appropriate AM or PM setting, and then press SELECT.

• 01B

Screen

Setup: This setting adjusts the contrast and brightness of the LCD screen to

accommodate the current lighting conditions and viewing angle.

Default settings: Contrast = 100%, Brightness = 50%
Range: 0-100%

Advertising