Using an AGS Module: Operation

STATUS

DESCRIPTION

Fault Temp

(FaltTemp or FTmp)

The generator failed to start in Start Temp mode.

Fault Test

(FaltTest or FTst)

The generator failed to start in Test mode.

Fault Time Daily

(Falt TOD or FTOD)

The generator failed to start in Start Time mode.

Fault Topoff

(Falt Top or FTop)

The generator failed to start in Start Topoff mode.

Fault VDC

(Falt VDC or FVDC)

The generator failed to start in Start Volts DC mode.

Fault 100% SOC

(Falt100% or F100)

The generator failed to start in 100% SOC mode.

Table 7-5, AGS Router Fault Statuses (Cont.)

04 AGS SETUP MENUS

DEFAULT SETTINGS

04A Gen Run Volts DC

Start Volts = 11.5 VDC (12v), 23.0 VDC (24v), 46.0 VDC (48v)

Start Delay = 120 secs

Stop Volts = 14.4 VDC (12v), 28.8 VDC (24v), 57.6 VDC (48v)

Stop Delay = 120 secs

04B Gen Run Time

OFF

04C Gen Run AC Amps*

OFF

04D Gen Run SOC

OFF

04E Gen Run Temp

OFF

04F Max Gen Run Time

12.0 Hrs

04G Gen Quiet Time

OFF

04H Gen Exercise

OFF

04I Gen No-Load Time

Warm-up = 60 secs

Cooldown = 60 secs

04J Gen 100% SOC

OFF

*MS-PAE, MS-PE and MSH Series models only

Table 7-6, AGS Default Settings on ME-RTR