Figure 3-12, CV Charge Done Time/Amps Charge Stages

* Set CV Charge Done Amps

This setting determines how long the charger will

hold the battery voltage at the CV Chg Volts setting—based on a minimum current setting

(i.e. done amps). During the Constant Voltage charge mode, as the battery charges, the

current from the charger slowly decreases. When this current decreases below the Set CV

Charge Done Amps setting, the charger transitions to the Silent charge stage. Most battery

manufacturers use a specifi c formula to determine the done amps that indicate a full charge

for their particular type of battery. The formula used by most manufacturers to absorb the

batteries is C/20, where C=Battery Bank’s Total Amp Hours. Basically, they take approximately

5% of the total battery bank size, and consider the battery totally charged when the charger’s

done amps drops to this level. Continuing to charge past this level may possibly overcharge

the batteries. Check with your battery manufacturer to fi nd out what the correct return amp

settings are for your batteries.

Note: After choosing the

Set CV Charge Done Amps selection,

the Set Max CC/CV Charge Time and Set DC Volts to Recharge settings must be determined.

Default: Amps = 20 ADC
Range: 0-250 ADC

Info: It is highly suggested that you install a battery monitor if the CV Charge Done

Amps setting is used. If a battery monitor is not installed, the CV Charge Done Amps

setting relies on the METER menu’s 01B Inv/Chg DC Amps value to determine when

to transfer out of the Constant Voltage charge mode. When a battery monitor kit (ME-

BMK/ME-BMK-NS) is installed, the CV Charge Done Amps setting relies on the METER

menu’s 05C DC Amps-BMK value to determine when to transfer out of the Constant

Voltage charge mode. This is the most accurate DC amperage measurement. The DC

amps reading from the battery monitor is accurate to +/ – .1 ADC.
Info: Setting the CV Charge Done Amps value to 0 (zero) will keep the charger in the

Constant Voltage charge mode until the Set Max CC/CV Time setting (under SETUP:

03C Battery Type/CC/CV) is reached.
Info: When using the CV Charge Done Amps setting, the charger will stay in the

Constant Voltage charge mode for a minimum of two minutes—even if the Done Amps

current is below the CV Charge Done Amps setting.
Info: If DC loads are connected directly to the batteries, it is not recommended that

you use the CV Charge Done Amps setting. DC loads cause the charger to increase the

amperage delivered to the battery bank in order to charge the batteries and to run the

DC loads. This scenario could result in overcharging the batteries since the done amps

reading will be skewed by the DC loads.

Constant

Current

Constant

Voltage

Silent

Constant

Current

Voltage

Current

Max Charge

Amps

CV Charge

Volts

Recharge

Volts

(restarts

Constant

Current

charge)

CV Charge Done

(= Time or Amps)

CURRENT & VOLTAGE

TIME